|
General:
To reduce danger
to personnel, and to reduce the heat generated by high AC
current, toroidal AC Current Transformers (also called transducers)
are inexpensive, common solutions. Generally speaking, these
devices, also known as "donuts", reduce the line current from
its rating to 5 amps AC. Thus the receiving instrument never
sees anything more than a maximum of 5 amps (amperage is the
killer; voltage is of lesser danger).
When using CT's,
one must make sure the load or burden that is connected to
the secondary is not above the limits of the CT. The load
limit is specified by its VA ratings (usually running from
2 to 10 VA). The larger the VA, the more resistance can
be tolerated by the CT. When in doubt, utilize a CT and a
CT transmitter
that converts AC amperage into a 4-20 mA DC signal for long
lead lengths (and specify compatible receiving instruments
scaled, however, in AC amps).
To calculate load:
- Resistance
of wire (typically, the CT comes with 24" of 16 AWG
wire; 16 AWG has a resistance of .0041 ohms per foot:
50 feet out and 50 feet back would 100 x .0041 = .41
ohms
- Resistance
of Analog or Digital Indicator/Recorder/Datalogger,
typically .1 ohm
- VA=I2R
(for example, 5 amps2 x
100 feet of 16 AWG= .41 + .1 for a meter= 10.5 VA
Therefore it is
obvious that any distances over a few feet from the CT should
mandate a transmitter.
*See
chart
Installation:
The donut transformer
can be ordered with mounting feet or flat bottom configuration
for surface mounting, or simply hung through the primary conductor
with one or more primary turns (see Ratio
Modification below).
Care must be taken
to ensure the secondary leads are connected at all times when
current is passing through the primary conductor.
Multipoint Switches:
In 3 phase systems,
the amp meter (0-5 ACA receiving instrument) can be switched
externally from phase to phase to monitor the various currents.
CAUTION: NEVER BREAK THE SECONDARY CIRCUIT OF A CURRENT TRANSFORMER
AS HUMAN LIFE AS WELL AS CONNECTED EQUIPMENT CAN BE ENDANGERED
BY INDUCED HIGH VOLTAGES. All Current Transformer Secondaries
must be short-circuited when not in use, and the S ampere
terminal of the meter-receiver connection must connect to
a secondary "BEFORE" the short is removed from that secondary.
Switches must "MAKE BEFORE BREAK", and must keep all unused
secondaries shorted. (Voltage switching is just the opposite--all
voltage switches must "break before make" and all unused potential
transformer secondaries should be kept open)
Common Characteristics
of CT's
- Frequency
affects a C/T only because the lines of flux generated
by the primary current begin to appear as DC as the
frequency gets very low; a C/T needs the AC CYCLE changes
to induce the secondary current. With anyone's toroidal
C/T, you will experience a drop in accuracy as the frequency
goes down from 60 Hz. One can manufacture a C/T with
an exotic metal core that is not quite as affected as
the silicon grain oriented steel most commonly used,
but the improvement would be questionable and at high
cost.
- Below 60
Hz, the accuracy will be affected by the drop in frequency
and voltage: with Instrument Transformers CT's having
the maximum acknowledged accuracy of 0.3% ANSI Rating,
you will experience a drop in accuracy at 9 Hz to 5%;
at 6 Hz it might be 7.5% of full scale. A Split Core
unit might have double the inaccuracy, or more (for example,
a 1% Split Core being used at 9 Hz will experience an
accuracy rating of 33% - {.3%/5% is as 1%/X or X = 5/.3
= 16.7 x 2}. Remember, it is difficult to come up with
test equipment with enough power to test full scale at
unusual frequencies. The lesson here is to take the most
accurate C/T you can if you are running in lower frequencies
than 60 Hz.
- Exercising
the C/T beyond its current rating for short periods is
not usually a problem; each CIT has a Thermal Rating
Factor (if not published, then you must assume it is
1.0). This is a "continuous thermal current rating factor".
The Instrument Transformer model 5A (page 5, Section
2) has a factor of 1.33 at 300C. This means this particular
C/T can be operated at 133% of its primary rated current
CONTINUOUSLY without overheating (a 200:5 can thus be
operated at 200 x 1.33 or 266 primary amps continuously).
Other CIT's have thermal rating factors of 1.5 and 2.0
etc. On a momentary basis, any CIT will usually operate
at 64 times its primary current rating for 1 second;
150 times its current rating for 1 cycle.
- Above 60
Hz, a CIT becomes conversely more accurate up to about
4000 Hz. Above this, you must examine the wave shape
carefully because it causes the core to saturate. 400
Hz is the published limit with some manufacturers; there
is usually no problem with accuracy or heat or saturation
at this frequency.
- 4-20 mA
DC Transmitters
- For
all such transmitters, an independent, stable
prime power is a requisite for published operational
accuracy and characteristics.
- The
internal transmitter of the device usually will
not operate below 85 volts (43 Hz)
- Frequency
response with a constant 120V 60 Hz Prime Power
starts to fall off at 20 Hz; by 9 Hz it will be
off by 5% Full Scale. At 6 Hz it will be off by
7.5% etc.
- P/T's and
Frequency: the ratio of voltage to frequency is important
to a P/T (but not to a C/T). It must remain constant,
or the P/T will overheat. Lesson: do not power a P/T
from a variable frequency drive unless this ratio can
be made constant.
AC
CURRENT TRANSFORMERS
HOW
TO OBTAIN SPECIAL RATIOS FROM STANDARD RATINGS
Window type current
tranformers are rated on the basis of a single primary turn.
However, other ratios are obtainable by the use of multiple
turns. Most window type current tranformers can have its nominal
ratio adjusted to a non-standard ratio by the use of primary
and secondary turns.
Primary
Turn Ratio Modification
Formula:
Ka = Kn x Nn / Na
Where:
Ka
= Actual Transformer Ratio
Kn = Nameplate Tranformer Ratio
Na = Actual Number of Primary Turns
Nn = Nameplate Number of Primary Turns
The
ratio of the current transformer can be modified by
adding more primary turns to the tranformer. By adding
primary turns, the current required to maintain five
amps on the secondary is reduced.
Example:
A 100:5 current tranformer designed for one primary
turn.
|
1
Primary Turn
NAMEPLATE
RATIO -- 100:5
ACTUAL RATIO -- 100:5
2 Primary Turns
NAMEPLATE
RATIO -- 100:5
ACTUAL RATIO -- 50:5
4
Primary Turns
NAMEPLATE
RATIO -- 100:5
ACTUAL RATIO -- 25:5
|
 |
|
Secondary
Turn Ratio Modification
Formula
: Ip/Is = Ns/Np
Where:
Ip
= Primary Current
Is = Secondary Current
Np = Number of Primary Turns
Ns = Number of Secondary Turns
Example:
A 300:5 Current Tranformer.
300
p / 5s = 60s / 1p
(In
practicality one turn is dropped form the secondary
as a ratio correction factor.)
The
ratio of the current tranformer can be modified by altering
the number of secondary turns by forward or backwinding
the secondary lead through the window of the current
tranformer.
By
adding secondary turns, the same primary current will
result in a decrease in secondary output. By subtracting
secondary turns, the same primary current will result
in greater secondary output.
Again
using the 300:5 example adding five secondary turns
will require 325 amps on the primary to maintain the
5 amp secondary output or:
325
p / 5s = 65s / 1p
Deducting
5 secondary turns will only require 275 amps on the
primary to maintain the 5 amp secondary output or:
275p
/ 5s = 55s / 1p
The
above ratio modifications are achieved in the following
manner:
|
TECHNICAL
DATA
CURRENT
TRANSFORMERS RATIO MODIFICATION
Relatively large
changes in ratio may be achieved through the use of primary
turns.
For example:
|
CT
RATIO
|
NUMBER
OF PRIMARY TURNS
|
MODIFIED
RATIO
|
|
100:5A
|
2
|
50:5A
|
|
200:5A
|
2
|
100:5A
|
|
300:5A
|
2
|
150:5A
|
|
100:5A
|
3
|
33.3:5A
|
|
200:5A
|
3
|
66.6:5A
|
|
300:5A
|
3
|
100:5A
|
|
100:5A
|
4
|
25:5A
|
|
200:5A
|
4
|
50:5A
|
|
300:5A
|
4
|
75:5A
|
A primary turn
is the number of times the primary conductor passes through
the CT's window. The main advantage of this ratio modification
is you maintain the accuracy and burden capabilities of the
higher ratio. The higher the primary rating the better the
accuracy and burden rating.
You can make smaller
ratio modification adjustments by using additive or subtractive
secondary turns. For example, if you have a CT with a ratio
of 100:5A. By adding one additive secondary turn the ratio
modification is 105:5A, by adding on subtractive secondary
turn the ratio modification is 95:5A. Subtractive secondary
turns are achieved by placing the "X1" lead through the window
from the H1 side and out the H2 side. Additive secondary turns
are achieved by placing the "X1" lead through the window from
the H2 and out the H1 side. So, when there is only one primary
turn each secondary turn modifies the primary rating by 5
amperes. If there is more than one primary turn each secondary
turn value is changed (i.e. 5A divided by 2 primary turns
= 2.5A). The following table illustrates the effects of different
combinations of primary and secondary turns:
|
CT
RATIO 100:5A
|
|
PRIMARY
TURNS
|
SECONDARY
TURNS
|
RATIO
ADJUSTMENT
|
|
1
|
-0-
|
100:5A
|
|
1
|
1+
|
105:5A
|
|
1
|
1-
|
95:5A
|
|
2
|
-0-
|
50:5A
|
|
2
|
1+
|
52.5:5A
|
|
2
|
2-
|
45.0:5A
|
|
3
|
-0-
|
33.3:5A
|
|
3
|
1+
|
34.97:5A
|
|
3
|
1-
|
31.63:5A
|
Questions? - Call John Perkins at 1-800-767-6051 |