 |
Microprocessor Based Installation
Practices --
Application Precautions
- Microprocessor based digital instruments
are more sensitive to poor installation practices than are
analog or older-type solid state instruments. Standard electrical
engineering practices must be rigidly observed if the advantages
of microprocessor based instrumentation are to be realized.
- Instrumentation power: The preferred
method is the use of a constant voltage transformer to establish
a 3-wire, 117 VAC power circuit consisting of safety ground,
neutral, and hot legs. The neutral should be tied to ground
at the transformer only. This circuit should have restricted
use for instrumentation, computers and other low current
draw equipment with steady-state amperage usage throughout
the plant. If this is not possible, power instrumentation
at each location with a separate isolation transformer.
Anti-surge protection is recommended.
- Signal Transmission: Physical electrical
wiring considerations include the mechanical isolation in
separate conduit of low voltage DC signals and power-supplying
higher voltage AC power wires. Shielded thermocouple extension
wire or extension wire in a separate, well-grounded conduit
should be used (you may run several pairs of T/C, RTD, or
low-current DC (4-20 mA, etc.) signal lines in the same
conduit, but never with power lines). Shielded and twisted
pairs may also be used, but the shield must be grounded
and grounded at one point only.
- Earth Grounds: The measured resistance
between earth grounds must be less than 5 OHMs.
- Avoid mounting instruments in the same
panel with high energy switching devices such as contactors,
motor starters or other line-spike inducing devices.
- Avoid ground loops on 4-20 mA DC control:
In a 4-20 mA DC current loop, only one ground point can
exist (all points must be "floating", also known as "Isolated",
"Differential", Push-Pull", I.E. ungrounded). That single
ground point is usually at the control. Do not assume that
the mAchine is properly grounded; check it.
- Inductive loads (I.E. relays, solenoid
valves, load contactors etc.) operated by the instrument
should be neutralized by using a resistor-capacitor (RC)
network across the load if the steady state current draw
is greater than 40 milliamps.
The values:
- Up to 70 mA, C: 0.047/0.05 Microfarad
R: 22 OHMs/2W
- Up to 150 mA: C: 0.1, R: 22 OHMs/2W
- Up to .5 A, C: 0.22/0.33, R: 47
OHMs/2W
- Up to 1 A, C: 0.47/0-5, R: 47
OHMs/2W
CPS should be 250 VAC operation, resistors
should be carbon.
- Signals from relatively rapidly transmitting
sensors may sometimes be delayed by slow moving responses
from control devices such as control valves. Rate action
can then cause instability. A general rule is if rate causes
instability at 30 seconds or less, remove the rate action
completely. A large proportional band may be necessary for
adequate control (400%).
|
|
|