|
Insulation
Resistance Testing For Maintenance & Safety
Insulation failure
can cause electrical shocks, creating a real hazard to personnel
and machinery. A regular program of testing insulation resistance
is strongly recommended to prevent this danger, as well as
to allow timely maintenance and repair work to take place
before catastrophic failure. All new equipment, motors, transformers,
switch gears, and wiring should be tested before being put
into service. This test record will be useful for future comparisons
in regular maintenance testing.
Some of the more
common causes of insulation failure include excessive heat
or cold, moisture, aging, corrosive atmospheres and vibration.
Insulation values are in ohms, and insulation values change
according to temperature. Take all of your readings at 20
deg C or at the same temperature, or correct for 20 deg C.
A general rule is to take 1/2 the resistance reading for every
10 deg C increase, and double the resistance for every 10
deg C decrease. For instance, if you measure 10 megohms at
30 deg C, a 10 deg increase, your true reading is 5 megohms.
Definitions:
Corona:
Partial discharge in a high-voltage field that does not bridge
the gap between the high voltage and ground, usually due to
a breakdown of a small area of insulation. This
discharge can often be seen and heard as a hissing
sound or glowing
around high-voltage cable and insulation during
wet weather.
Dielectric:
All materials can be considered conductors of electricity;
some are better conductors than others, and the difference
between an insulator and a conductor is the dielectric or
"resistance", i.e. the amount of force required to move free
electrons.
Dielectric Test
Set: Usually DC medium voltage insulation resistance testing
up to 7.5 kV with fast charging of high capacitance samples.
Often used to compare the absorption characteristics of humid
or otherwise
contaminated insulation. Test voltages are applied and varied
over extended periods, drawing a curve showing the resistance
value versus time.
DLRO: Digital
Low Resistance Tester to 0.10 micro-ohm for measuring resistance
of switch and circuit breaker contacts, winding resistance
of transformers and motors, busbar and other joint resistance,
bonding material, splices, welds and
fuses, graphite electrodes and cracks in squirrel cage rotors.
Earth Tester
(Ground Resistance Tester): Measurement of Resistance
of Ground Connections to Earth and for Determining Earth Resistivity
effectiveness and integrity. Used to test grounds of utility
poles, distribution transformers, telephone and CATV systems,
Computers, Machinery, Antennas, Portable Generators. Usually
operated with accessory kits containing Ground Probes &
Test Leads. Having a good ground is critical for some
equipment types; not having a good ground is a safety
issue. Four Terminal Earth testers can also be used to prospect
for geophysical properties; to locate ore bodies, clays and
water bearing gravel beneath the soil, as well as the depth
of bedrock and thickness.
Megger: While
there are many brands of insulation testers, there is only
one "MEGGER"; it is a registered trademark of AVO Biddle.
Megohmmeter:
Insulation Testing Device, usually 500 or 1000 V DC Non-Destructive
Testing
One Megohm Rule:
Suggested based upon equipment rating:
< 1000 V = 1 megohm minimum
> 1000 V = 1 megohm/1000 Volts
High-Pot Tester
(High Potential): AC and AC/DC types. AC Charging current
is extremely large with minor leakage current. Sometimes this
is called destructive testing in that voltage is increased
to some specific point to see if the insulation can withstand
that particular voltage. It is a Go/No Go type of test, and
can cause deterioration of the insulation, as opposed to the
DC non-destructive test megohmmeters. AC versions are often
used to test the dielectric strength of electrical insulation
and ground circuit continuity of 3-wire appliances , tools,
lighting fixtures and lamps, heating elements.
Such tests are
required by UL; such Hipot Testers should carry safety interlocks
because they are often used by non-technical personnel.
DC High-Pot testing
is superior to medium voltage testing because it stresses
the insulation at or above the working level, providing more
information about the condition of the insulation and helping
you to predict problems before a breakdown occurs. The tests
are more complicated and the instruments more expensive,
but the condition of the apparatus in question is better documented
and tested and less likely to fail without warning.
Test Procedures:
1. Proof
Test: Simple Go-No Go procedure; if the insulation is
good, it will not fail.
2. Insulation
Resistance Test: Regular testing to determine gradual
decrease in insulation resistance. This provides a means
for predicting future insulation failure.
3. Polarization
Index Test: For testing high capacitance systems such
as large motors, generators, or apparatus with complex insulation
systems. Steady readings are only possible after the time-dependent
currents have almost died down. Test
measures the ratio between insulation resistance
readings taken at one minute and ten minutes
after the application of voltage to judge the rate of disappearance
of capacitance and absorption currents. A ratio known as
the polarization index can be obtained by dividing the value
from the 10 minute reading by the value from the one-minute
reading. A low polarization index usually indicates excessive
moisture and contamination. On large motors or generators,
values as high as 10 are commonly expected.
4. Step Voltage
Test: Provides more information about the insulation
than any other test; measures the current at several different
levels of voltage to provide a trend or curve to predict
need for repair or replacement. Step increases with two
or more voltages @ 1:5 ratio, each step lasting 60 seconds.
Facts about
Insulation Testing:
1. The commonly
used DC test voltages
for AC rated equipment are:
| up
to 100 Volts |
100
or 250 Volts DC |
| 440-550
Volts |
500
or 1000 Volts DC |
| 2400
Volts |
1000-2500
Volts DC |
| 4160
Volts |
1000-5000
Volts DC |
Readings will never
be the same unless the specimen is discharged (4-5 times test
period). 500 VDC is the most commonly required voltage since
it is used to test all circuits except low voltage circuits
with a nominal voltage up to and including 500 Volts. A 250
VDC test capability is necessary to test low voltage circuits
supplied by an isolation transformer. A 50 Volt range will
allow testing delicate components and equipment with up to
55 V of electrical interference, or cross talk.
2. Test or Proof
voltages for equipment is considerably higher than used for
routine maintenance testing. The rule of thumb:
DC maximums can
be determined by the following formula:
Equipment before
being put into service
Factory AC Test
= 2 x Nameplate + 1000 Volts
DC proof test
or insulation
0.8 x nameplate x 1.6
DC proof test
after service 0.6
x nameplate x 1.6
Example:
Motor with 2400
Volt AC nameplate
Factory AC test=
2 (2400)
+ 1000 = 5800 VAC
Maximum DC test
of Insulation: 0.8
(5800) 1.6 = 7242 VDC
Max DC test after
service: 0.6
(5800) 1.6 = 5568 VDC
3. There are 3
types of current that appear in insulation testing:
A. Capacitance
Charging Current
This
is the current which is like a condenser, which starts out
high and tapers off rapidly to zero.
B. Absorption
Current
This is due
to the polarization of the insulating materials. It takes
longer for absorption current to reach a static point
than charging current and, likewise, takes a much longer
time to bleed off. On large or long cables it is important
to short out the cable after test to eliminate the possibility
of shock to the person conducting the test.
C. Leakage
Current
This is the
current we are really concerned about. It is a steady
current leakage through or over the insulation due to
moisture, dirt, or other reasons. This test must be continued
for one minute or until the reading holds steady for 15
seconds. This assures us that the capacitative and absorption
currents have reached a static point. This will vary with
the equipment under test. Motors and transformers will
take longer than average conductors.
4. Megger Insulation
Testers come in three basic types: Hand crank, Line or Motor
operated, or Battery (or in combination). Battery or AC is
preferred for tests one minute or longer in duration.
5. Danger:
A. All equipment
under test MUST be disconnected and isolated.
B. Equipment
should be discharged (shunted or shorted out) for at least
as long as the test voltage was applied in order to be absolutely
safe for the person conducting the test.
C. Never use
an Insulation Tester in an explosive atmosphere.
D. Make sure
all switches are blocked out and cable ends marked properly
for safety.
6. Manuals on Electrical
Insulation Testing for the Practical Man are
available from us through AVO Biddle:
A. A Stitch
in Time-The Complete Guide to Electrical Insulation Testing
B. The Lowdown
on High-Voltage DC Testing
C. Getting
Down to Earth
|