|
Relative Humidity
Definition:
Humidity is a term describing the amount
of water vapor or moisture being carried by air. Measurement
can be either absolute or relative; absolute measurement deals
with the weight per unit of volume of water vapor whereas
relative measurement deals with the condition of saturation,
usually stated in percent. At 100% RH, the air is completely
saturated with water and no evaporation is taking place.
Relative Humidity is a relative measurement!
The total amount of water vapor that air can hold is dependent
upon its pressure and temperature. At a pressure of 30.11
Hg, air at O deg F will hold about 1/2 grain of water vapor
per cubic foot; at 32 deg F, about 2 grains, at 70 deg F,
about 8 grains; and at 100 deg F, about 20 grains. A grain
is 1/7000th part of a lb of water.
Under normal conditions of pressure at
70 deg F, a cubic foot of space can hold 8 grains of water
vapor. Therefore, air with only 2 grains has only one-fourth
of its maximum capacity, or a RH of 25%.
Dewpoint is a temperature at which air
in the atmosphere becomes saturated with water vapor and starts
to condense. Any lowering of temperature below the dew point
results in condensation of some of the water pressure present.
Relative Humidity at the dewpoint is always 100%.
Measurement Considerations
and Solutions
Wet bulb- Drybulb:
Time honored method whereby one of a matched
set of thermometers is constantly wetted by a fabric wick
connected to a cistern filled with distilled water and is
compared to the other thermometer. The wet-bulb draws water
to it by capillary action, and evaporation takes place from
around the bulb of this thermometer, the rate being governed
by the dryness of the surrounding air, and heat is given up,
with the result that the dry-bulb thermometer reads higher
than the wet-bulb thermometer. The difference between the
two matched thermometers determines the relative humidity
from pyschrometric charts. The thermometers should be located
where there is a reasonable amount of air circulation. Any
device using this technology should have forced air fan action
of about 600 FPM; applications having less air circulation
will have a slower response and lessened ability of the wetbulb/drybulb
to respond to relative humidity changes. Care should be taken
that the wetbulb/drybulb is not placed near heat sources,
including direct sunlight.
Important Considerations:
Care must be taken to keep the wick clean
and supplied with clean, preferably distilled, water. Soluble
salts and dirt particles accumulated on the wick adversely
affect the rate of evaporation and capillary causing inaccuracies
in the wet-bulb readings. Wash the wicks frequently; discard
and replace when the material becomes hard.
Fixed-Position Hygrometers: Rapid circulation
of air around the bulbs just prior to reading is absolutely
vital for accuracy. Use a hand-fan or other device for one
minute or more, then immediately take the reading. Make sure
that the reading is done at eye-level so that the thermometer
is correctly addressed. Read the WET-BULB first, then the
DRY-BULB.
Typical instruments:
The Taylor Mason's Hygrometer is a wall
mount wet/dry bulb instrument.
The Sling Psychrometer has a folding swivel
handle for use to "sling" around to mimic rapid air circulation.
To use it, one first saturates the wicking of the wetbulb
with water at room temperature. The Psychrometer is whirled
for 15 to 20 seconds, holding it away from the body and from
any objects it might hit. Immediately read the wetbulb and
then the drybulb thermometers and note; repeat until two or
more readings agree at the lowest indication obtainable. The
wicking must be kept perfectly clean and thoroughly saturated
to secure accurate indication.
For remote reading, computer input, digital
displays, or very high temperature applications, matched 100
ohm Platinum RTD's with transmitters can be used instead of
thermometers and the outputs put into an adder-subtracter
transmitter for a net output. Our Digital Panel Meters can
be calibrated to read out directly in relative humidity. We
even offer a round chart recorder from Partlow that will take
the wetbulb/drybulb inputs directly from RTD'S, Thermocouples
or Temperature Transmitters. It uses an algorithm to automatically
calculate relative humidity.
Direct Reading, dial indicators using
either Goat's hair or synthetics which are hydroscopic are
readily available. These devices have carefully chosen materials
which change length in the presence of moisture, and convert
this lateral movement into a rotary motion of the hand on
the dial. Direct reading types have the advantage of fast
response. The disadvantage is in the higher cost and, in general,
lower accuracy, and a narrow operating temperature range.
Digital Hand Held Instruments utilize
hydroscopic capacitance polymers which complete a variable
voltage electronic circuit. Advantages are the ability to
store 16 readings ( Model THIOO ), rapid response, temperature,
humidity and dewpoint readings, and the unit can be calibrated
@ 12% and 75% with the A834 Calibration Kit.
Data Loggers with Software perform months
of unattended monitoring and are available (with or without
sensors) from stock.
Round Chart Recorders, either self-contained
or with remote sensors, are available from stock. These can
be either mechanical devices or utilize electronic capacitance
technology.
R.H. and Temperature Transmitters are
stock items too.
Whatever your relative humidity requirements
are, give Branom a call!
Relative Humidity Tables (Publication
Number PB257-023/2) can be ordered from:
National Technical Information Service
Department of Commerce
Springfield, Va 22161
Re: 200 Degrees F Relative Humidity (September
11, 1998)
Beyond the capabilities
of RH Transmitters
One way to attack the high temperature
problem with relative humidity is to take a modern day twist
on the age-old wet/dry bulb method of measuring relative humidity.
The first thing you need is a Taylor Water
Cistern #5522N and some Taylor Wicks, or any kind of semi-enclosed
water vessel and cotton wick.
The wetbulb must, of course, be kept wet,
either through manual filling or direct coupled to some tubing
with a water source and a needle valve. A quality wick, such
as the Taylor, will pull the water from the cistern via capillary
action, and keep the wetbulb wet.
Then we need two matching output RTD's,
which must be tested at 200 Deg F. We normally would utilize
the heavy duty Gordon # RFJBOTK14OBB300 with 30 feet of Extension
Wire.
The output of the two RTD's would become
the inputs for the API Transmitter, a two input (RTD, T/C,
linear etc) device with advanced math capabilities. It will
take the two RTD inputs, and using the level one math will
deduct the wetbulb temperature from the dry bulb, and then
the remainder would be massaged to the relative humidity table
(see below) for the temperatures to be measured, i.e. 190-210
degrees F. This would then be converted in the second level
to a direct output of 4-20 mA DC corresponding to Relative
Humidity. The 4-20 mA Signal then would become the input to
the Red Lion PAXP Digital Panel Meter, which has 16 points
of linearization, whereby the non-linear 4-20 mA signal can
be linearized. The PAXP is available with up to 4 alarms,
retransmitted 4-20 mA or DCV outputs, or RS232, RS485 or DeviceNet.
Calibrated. For recording, Partlow makes a 12" Round Chart
direct reading from RTD wetbulb/drybulb Recorder #MRC7700.
All of these items, except the Partlow,
are normally Seattle Stock; with calibration and setup, possibly
two days or so maximum delivery. The Partlow is usually one
week ARO.
The
Method of Dewpoint Temperature
When
measuring Humidity, it is often necessary to determine the
dew point temperature.
The
following table shows the relationship between Relative Humitidy
and Temperature.
|
14 deg F
|
32 deg F
|
50 deg F
|
68 deg F
|
86 deg F
|
104 deg F
|
122 deg F
|
140 deg F
|
| 10% Rel Hum |
--
|
--
|
-4.5
|
9.5
|
23.4
|
36.9
|
50.2
|
63.3
|
| 20% Rel Hum |
--
|
-4.7
|
10.8
|
25.5
|
40.5
|
55.0
|
69.4
|
84.0
|
| 30% Rel Hum |
--
|
4.1
|
19.7
|
35.4
|
50.9
|
66.9
|
81.9
|
96.8
|
| 40% Rel Hum |
-6.2
|
10.4
|
26.6
|
42.8
|
58.8
|
74.8
|
90.7
|
106.5
|
| 50% Rel Hum |
-1.3
|
15.3
|
32.0
|
48.6
|
65.1
|
81.7
|
97.9
|
114.4
|
| 60% Rel Hum |
2.7
|
19.8
|
36.7
|
53.6
|
70.3
|
87.4
|
104.2
|
120.9
|
| 70% Rel Hum |
6.1
|
23.4
|
40.6
|
57.7
|
75.0
|
92.3
|
109.4
|
126.5
|
| 80% Rel Hum |
9.0
|
26.4
|
44.1
|
61.5
|
79.0
|
96.6
|
113.9
|
131.5
|
| 90% Rel Hum |
11.5
|
29.3
|
47.1
|
64.9
|
82.8
|
100.4
|
118.2
|
136.0
|
| 100% Rel Hum |
13.8
|
31.8
|
49.8
|
68.0
|
86.0
|
104.0
|
122.0
|
140.0
|
Example: Temp 32 deg
F, Humidity 50%RH --> Dew Point is 15.3 deg F
|