|
SOLID STATE RELAYS
AND SCR POWER CONTROLLERS
Introduction
Solid State Relays
(SSR's) and SCR's (Silicon Controlled Rectifiers, also called
Thyristors) are becoming more popular all the time to replace
mechanical relays and contactors and mercury relays due to
their relatively low cost, lack of moving parts, and their
lessened wear and tear on heating elements. Zero fired devices
(SSR's and some SCR's) do not send a large spike down the
electrical line every time they turn on, like mechanical relays
do, and the contacts do not erode due to arcing (no arcing
occurs with SSR's and SCR's). Phase angle fired SCR's do cause
spikes, however, as well as possible harmonic distortion on
the line, so care must be given with their placement.
Zero Fired Devices
- Solid
State Relays (SSR's)
For single
phase resistance (electrical heating element) heating,
solid state relays with ratings of 10, 25 and up to 100
amps @ 120-240V (480V also available) are commonly utilized.
These incorporate two Zero Fired SCR's which provide zero
voltage turn-on and zero current turn-off, which practically
eliminates any spike generation when the load is turned
on or off. Since these are solid state relays, they do
not wear out like a mechanical relay. However, their amperage
capability must be derated considerably if the environmental
temperature increases beyond normal ambient (i.e. if they
are mounted in a confined space without convection "heat
sinks" or external cooling). Also, during the "off" state,
some leakage, say 1 milliamp AC, usually takes place,
which might trigger some sensitive devices. This is never
a problem with resistive heaters; however, with a coil
of a contactor or a motor, this could be a problem (some
SSR's are 120V prime power and thus switch like a relay
with a 120VAC coil). One other caveat: when these devices
fail, they tend to fail closed, keeping the circuit operating.
For processes where this is unacceptable, an FM approved
Hi-Limit Alarm and thermocouple should be included to
shut down an overheating situation. The standard input
to a SSR is a 3-32 VDC pulse train from a SS output (gating)
controller.
- SCR Power
Controller
SCR Power Controllers
are available either as Zero Fired (for resistive loads)
or Phase Angle Fired (for transformer coupled loads and
some heating loads which change resistance dramatically
with temperature or time), and single or 3 phase loads.
- Zero-Fired
- General
Most power
control applications involve simple resistive heating
loads which require little in the way of sophistication.
They undergo negligible resistance change as they heat,
and they operate at or near available line voltages.
Modern controllers often offer a line voltage variation
feedback correction to offset this. Precise temperature
control is the main reason for selecting an SCR, as
it modulates the power flow into the elements as needed.
By electrically switching an SCR on at the AC sine wave
zero crossing point, it remains on through the half
cycle of the sine wave and commutates off at the next
zero crossing. This duplicates the action of a contactor,
but at a much faster rate and without the electrical
noise and mechanical contacts wear and tear. The important
fact to be noted is that since the SCR is turned on
at or nearly at the zero crossing point, no power is
being switched under load. This results in virtually
no EMI generation. Also, the fast rate of fire lessens
thermal shock and maintains temperature much better
than mechanical relays. Standard Zero-Fired SCR's take
a 4-20 mA DC control input; 0-10 VDC and DC pulse trains
are other possibilities.
- Single
Phase Control
By controlling
the number of cycles of a fixed time period (microseconds
in some units), the control signal to the SCR will cause
the SCR to be gated on for a certain time period and
then off for a given time period. For example, at 50%
power, it will be on for 10 cycles and off for 10 cycles.
At 10% power, it will be on for 2 cycles and off for
18, etc. It is important to note that zero fired SCR's
control average power to the load. There is no
voltage or current control as in phase control (although
this is available in some controllers). It is, therefore,
not practical to current limit zero fired SCR's. Of
course, with purely resistive loads, there is no need
for current limiting. More exotic SCR's offer Fast Cycle,
Half Cycle or Single Cycle firing.
- Three
Phase Control
Confusion
occasionally results when users notice that three phase
zero fired SCR's often control only two legs of the
three phases. This is standard practice throughout the
industry and results from the fact that in common wye
or delta connected loads, current flow through the third
leg must also flow through the other controlled legs.
This effectively controls all power to the load, and
results in some cost saving.
- Prohibited
Load
Transformers
head the list as prohibited for most Zero Fired devices.
As a power transformer is energized, a magnetizing current
flows into the primary winding to set up flux lines
within the transformer so that power may be taken from
the secondary. This inrush of current may be several
times the surge current rating of the SCR and fusing.
This is why "soft start" or "ramping on startup" features
are specified with controllers dealing with phase controlled
SCR's. The voltage is started at a small percentage
of the line voltage and is slowly brought up to the
line value, so that inrush currents can never exceed
ratings. Units turn fully on at zero, and therefore,
cannot be prevented from impressing the entire inrush
current upon the transformer. The inevitable result
is a blown fuse or a damaged SCR and transformer.
Four wire
wye loads also present problems. Think of them as
three separate and independent loads. A four wire
wye (or "star") load has each phase connected to a
neutral point; therefore, the voltage across the leg
is the line voltage divided by 1.732. That is, on
a 480V 3 Phase system connected 4 wire Wye, three
277 volt units must be used. They will be connected
from line to neutral. Some SCR's, however, are designed
for use with 3 or 4 wire Wye, open or closed Delta,
3 wire Delta and Star loads. Just make extremely sure
that they are designed for this purpose.
Any heating
element which requires current limiting may not be
controlled by standard zero fired devices. Such elements
include: molybdenum, tantalum, silicon carbide (globars),
super kanthal, and platinum. All of these exhibit
a significant resistance change over time and temperature,
usually from 2 or 3:1 to 20:1. These nearly always
have an interposing transformer in the system and
as such will be eliminated from zero fired consideration.
Any load,
such as a tungsten lamp, which has a minimal resistance
change, but which has a very fast response time, may
not be zero fired.
Generally
speaking, any three phase load which tends to be unbalanced,
or any resistance load with a high temperature coefficient
and significant thermal mass, cannot be operated zero
fired.
- Phase
Angle Fired
Basically, motors
or transformer-coupled loads must be fired by a phase
angle gating device because at start-up, lots of power
is necessary to energize the coil before any work can
be done. The inrush of current for this would blow the
fuses of a zero-fired device, or even blow it up. Certain
electrical connections and heating elements also must
be phase angle fired. Any prohibited load for a zero fired
device is a candidate for phase angle firing.
Whereas zero
fired devices turn on at each zero crossing point in
the AC sine wave, and control by regulating bursts of
whole sine waves to the load, phase angle fired devices
may be turned on at any point within the half cycle.
This controls the RMS voltage out of the SCR, and thus
the power. See Figure 1. The ability
to choose any of an infinite number of firing points
is sometimes called stepless control. This allows Phase
Angle Fired SCR's to replace Saturable Reactors, Variacs,
Stepper Switches, Contactors, Ignatrons, and Thyratrons
with a much more stable, reliable, efficient and acoustically
quieter device.
When an SCR
is fired at some conduction angle other than zero, let's
say 90°, large amounts of power are being switched
under load. If the SCR is driving a transformer, this
steep waveform will permit a very large inrush current
to flow into the transformer primary. This may be several
times the surge current rating of the SCR, fuse and
transformer. Similarly, if under steady state operation,
the power line drops out for a few cycles, the power
may be reapplied to the transformer when the flux is
at an extreme in the hysteresis curve; this may drive
a transformer into saturation. Again, this saturation
will cause very large and potentially damaging currents
to flow.
Instead of
impressing the full line voltage on the transformer,
the SOFT START feature of a phase angle SCR will slowly
increase its output from zero to full line voltage over
a 12 cycle period, so that the transformer core has
time to magnetize before taking full power from the
secondary (See Figure 2). This occurs
each time the power control is turned on, each time
there is a momentary outage on the power line, say a
soft start reset, or even after a very large step change
in the control signal.
To protect
the load, current limiting should be considered with
a phase fired power control. This feature overrides
any other control signal over a selectable range and
shuts the system down if the watt density rating of
the heater load is exceeded by the power flowing into
it. Fast gating limit monitors currents above a prescribed
level and limits gate pulses to the SCR to prevent damaging
currents.

Figure 1: Four possible conduction angles
from infinite possibilities

Figure 2: Approximation of Soft-Start
|