Representative photo. Please check item description for details.

0-1" WC, DP TRANSMITTER, 4-20MA OUTPUT

https://www.branom.com/web/image/product.template/161638/image_1920?unique=7e6d319
(0 review)

Manufacturer: Dwyer Instruments Inc

Mfg Product Code: 607-3

Weight: 1.2 lb(s)

On Hand: 4

Series 607 Differential Pressure Transmitter combines very low ranges with exceptional stability, reliability and either ±0.25% or ±0.5% accuracy for the most demanding applications. Ranges from 0-0.1" to 0-25" w.c. Ultra thin glass clad silicon diaphragm design resists shock and vibration, practically eliminates drift. Certification to NIST standards is included with each unit. Tough stainless steel housing is NEMA 2 rated to protect against moisture and dirt. Use with air and other compatible gases.

  • Service: Air and non-conductive, non-corrosive gases.
  • Wetted Materials: Consult factory.
  • Accuracy: ±0.5% or ±0.25% FS.
  • Stability: ±0.5% FS/yr.
  • Temperature Limits: -20 to 160°F (-29 to 71°C), 10 to 95% RH.
  • Pressure Limits: 10 psig (0.69 bar).
  • Compensated Temperature Range: 35 to 135°F (2 to 57°C).
  • Thermal Effects: ±0.015% F.S./°F (zero and span).
  • Power Requirements: 12 to 36 VDC.
  • Output Signal: 4 to 20 mA DC, 2-wire.
  • Zero and Span Adjustments: Externally accessible potentiometers, non-interactive, ±10% F.S. adjustment.
  • Response Time: 250 ms max.
  • Loop Resistance: 0 to 1045 ohms Vmin=12V+[(.22A)(RL)].
  • Current Consumption: 3.6 mA (min).
  • Electrical Connections: Screw terminals.
  • Process Connections: Barbed stainless steel for 3/16" I.D. tubing.
  • Housing: 300 Series stainless steel (NEMA 2).
  • Weight: 1.04 lb (472 g).
  • Agency Approvals: CE.
  • 777.00 777.0 USD 777.00

    777.00

    Not Available For Sale

    • Brand
    • Accuracy
    • Max Operating Pressure
    • Max Operating Temperature
    • Measurement Minimum
    • Output Communication Protocol
    • NEMA / UL

    This combination does not exist.


    Product Datasheets

    Datasheet 1

    0-1" WC, DP TRANSMITTER, 4-20MA OUTPUT

    • Brand
    • Accuracy
    • Max Operating Pressure
    • Max Operating Temperature
    • Measurement Minimum
    • Output Communication Protocol
    • NEMA / UL

    777.00 777.0 USD 777.00

    777.00

    Not Available For Sale

    This combination does not exist.



    Brand:Dwyer
    Accuracy:- ±0.25% or ±0.5% FS
    Max Operating Pressure:10 psid
    Max Operating Temperature:160 °F
    Measurement Minimum:0
    Output Communication Protocol:4-20 mADC
    NEMA / UL:NEMA 2


    Specifications

    Brand Dwyer
    Accuracy - ±0.25% or ±0.5% FS
    Max Operating Pressure 10 psid
    Max Operating Temperature 160 °F
    Measurement Minimum 0
    Output Communication Protocol 4-20 mADC
    NEMA / UL NEMA 2