    Description

    Red Lion's Sixnet® series of RTUs provide powerful control in industrial automation applications. The product line is made up of the IPm®, mIPm, IPm2m®, and uIPm series of industrial RTUs. With a variety of connectivity, I/O, and programmability there is an industrial RTU for the toughest applications.

    Features

    Performance Specifications

    • Industrial PowerPC (32 bit data bus)
    • Operating system embedded open-source Linux
    • Dynamic memory (RAM) 32 Mb for program execution, dynamic variables, dynamic file system, etc.
    • Program memory (Flash) 32 Mb for Linux OS, program storage and file system
    • Retained memory (RAM) 512K (battery-backed) for datalogging and retained variables
    • Real-time clock battery-backed for time stamping and other operations
    • I/O Expansion RS-485 or Ethernet
    • Datalogging support
    • IEC 61131 programming, ISaGRAF for ladder logic, SFC, flow charting and more (6 languages supported)
    • High Level C programming

    Ethernet Port 

    • 10/100BaseTx (auto-detecting)
    • RJ45 connection (auto-crossover)
    • Protocols TCP / IP, ARP, UDP, ICMP, DHCP, Modbus / TCP, Sixnet®, optionally PPP, DNP3, IEC60870-5-101/104 and more

    Serial Port 

    • Up to 115,200 baud
    • RS-485 Port A screws (485+, 485-, GND) (2-wire half-duplex)
    • RS-232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
    • Protocols Master and slave modes; Sixnet and Modbus RTU / ASCII; optional: Slave; DNP3, IEC60870-5-101/104. Others available as Linux applications

    Discrete Inputs

    • 12 channels sourcing or sinking (jumper/software selectable)
    • Guaranteed ON voltage 9 VDC
    • Maximum voltage 30 VDC
    • Guaranteed OFF voltage 5.0 VDC and 1.5 mA DC
    • Input resistance and current 10K Ohms and 3 mA @ 24 VDC
    • Filtered ON/OFF delay 25 mS (20 Hz max. counting) for contact bounce filtering
    • Fast ON/OFF delay 4 mS (100 Hz max. counting)
    • Count rate (see above) (10 KHz on channel 1 only)
    • Counter modes pulse, rate and run time
    • Poll time (all channels) 5 mS to 20 mS configuration dependent

    Discrete Outputs

    • 4 channels – sourcing 10-30 VDC
    • Min. and max. output load 1 mA to 1 Amp sourcing per channel
    • Max. OFF state leakage 0.05 mA
    • Inrush current 5 Amps (100 mS surge)
    • Typical ON characteristics 0.3 Ohms resistance and 0.3 VDC voltage drop @ 1A
    • Poll time (all channels) 5 mS to 20 mS configuration dependent

    Analog Inputs

    • 8 channels – current or voltage selectable
    • Full scale range 4-20 mA or 0-5 VDC (jumper selectable)
    • A/D and input resolution 16 bits (0.003%); 2 uA (current range) or 0.5 mV (voltage range)
    • Full scale accuracy +/-0.1% (@20°C) (factory calibration)
    • Span and offset temp. coeff. +/-50 ppm per °C
    • Input impedance 100 Ohm (current range), 80 K Ohm voltage
    • Current protection Self-resetting fuses (for 4-20 mA range)
    • DMRR 66 dB at 50/60 Hz (differential mode rejection)
    • CMRR (common mode rejection) Not applicable since analog inputs are single ended.
    • Fastest update time 50 mS (both channels) – configurable for longer integration times for better noise filtering

    Environmental

    • DIN-rail or panel-mount
    • Input power 10-30 VDC
    • Input current 100 mA @ 24 VDC (typical)
    • Temperature -40 to 70°C (-40 to 85°C storage)
    • Humidity 5% to 95% RH (non-condensing)
    • Flammability UL 94V-0 materials
    • Electrical safety UL 508, CSA C22.2/14; EN610101; (IEC1010)
    • EMI emissions FCC part 15, ICES-003, Class A; EN55022; EN61326-1
    • EMC immunity EN61326-1 (EN61000-4-2,3,4,6)
    • Surge withstand IEEE-472 (ANSI C37.90)
    • Vibration IEC68-2-6
    • Hazardous locations (Class 1, Div 2, Groups A,B,C,D) UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
    • Tested to Marine/offshore standards