Representative photo. Please check item description for details.
FCI Model ST51 Biogas & Natural Gas Insertion Thermal Mass Flow Meter
Models ST51 and ST51A are a compact, low cost solution for accurate, repeatable flow measurement of biogas, digester gas, landfill gas, methane and natural gas as well as air, compressed air or nitrogen. This insertion-style flow meter has no moving parts and is available in probe lengths for installation into pipe diameters from 2.5 inches to 24 inches [63 mm to 610 mm]. It is easily connected into the pipe via a 1/2 inch or 3/4 inch NPT compression fitting. ST51 uses constant power thermal dispersion drive technology, with a slightly heated sensor, which uniquely provides a subtle drying effect on the sensors that results in effective measurement in moist gas applications.
The ST51 Series electronics are housed in rugged, IP67 rated enclosure with dual conduit ports in either NPT or M20 threading. The instrument comes standard with dual 4-20 mA, NAMUR NE43 complaint outputs and a 500 Hz pulse output. The model ST51A adds HART or Modbus, a higher process temperature service range, a SIL compliance rating and extended warranty. The transmitter/electronics can be integrally mounted with the flow element (probe) or be remote mounted to best match your installation situation. The complete instrument carries global Ex agency approvals for Division l/Zone 1 installations.
The ST51 flow sensing element features precision, platinum RTD in small diameter, "equal-mass," all-metal thermowells to provide superior accuracy, repeatability and fast response.
Models ST51 and ST51A are a compact, low cost solution for accurate, repeatable flow measurement of biogas, digester gas, landfill gas, methane and natural gas as well as air, compressed air or nitrogen. This insertion-style flow meter has no moving parts and is available in probe lengths for installation into pipe diameters from 2.5 inches to 24 inches [63 mm to 610 mm]. It is easily connected into the pipe via a 1/2 inch or 3/4 inch NPT compression fitting. ST51 uses constant power thermal dispersion drive technology, with a slightly heated sensor, which uniquely provides a subtle drying effect on the sensors that results in effective measurement in moist gas applications.
The ST51 Series electronics are housed in rugged, IP67 rated enclosure with dual conduit ports in either NPT or M20 threading. The instrument comes standard with dual 4-20 mA, NAMUR NE43 complaint outputs and a 500 Hz pulse output. The model ST51A adds HART or Modbus, a higher process temperature service range, a SIL compliance rating and extended warranty. The transmitter/electronics can be integrally mounted with the flow element (probe) or be remote mounted to best match your installation situation. The complete instrument carries global Ex agency approvals for Division l/Zone 1 installations.
The ST51 flow sensing element features precision, platinum RTD in small diameter, "equal-mass," all-metal thermowells to provide superior accuracy, repeatability and fast response.
Your Dynamic Snippet will be displayed here...
This message is displayed because youy did not provide both a filter and a template to use.
Alternative Products
Specifications
| Display Type | Integral, Remote, Blind |
| Power Supply | 85-265 VAC, 18-36 VDC |
| Electrical Connection | Two 1/2" NPT Cable Entries, Two M20x1.5 Cable Entries |
| Pipe Orientation | Horizontal, Vertical |
| Flow Direction | Left -> Right, Right -> Left, Up, Down |
| Mounting Orientation | Top, Side - Facing Up, Side - Facing Down, Left Side, Right Side |
| Temperature | Standard: 40 to 100°F | 4 to 38°C, Extended Temperature: 0 to 250 °F | -18 to 121°C |
| Gas Type | Biogas, Digester Gas, Natural Gas, Methane, Flue Gas, or Other Hydrocarbon Mixed Gases, Air, Nitrogen or Compressed Air |
| Enclosure Style | [1] Blind/VDC/NPT, [2] Blind/VAC/NPT, [3] Integral/VDC/NPT, [4] Integral/VAC/NPT, [7] Remote/VDC/NPT, [8] Remote/VAC/NPT, [A] Blind/VDC/M20, [B] Blind/VAC/M20, [C] Integral/VDC/M20, [D] Integral/VAC/M20, [E] Remote/VDC/M20, [F] Remote/VAC/M20 |
| Mounting Style | [F] Horizontal/L-R/Top, [G] Horizontal/R-L/Top, [H] Horizontal/L-R/Side Up, [J] Horizontal/R-L/Side Up, [K] Horizontal/L-R/Side Down, [L] Horizontal/R-L/Side Down, [M] Vertical/Up/Left, [N] Vertical/Up/Right, [P] Vertical/Down/Left, [R] Vertical/Down/Right |
| Process Connection/Ferrule Material | [1] 1/2" NPT, Compression Fitting, Teflon Ferrule, [2] 1/2" NPT, Compression Fitting, Metal Ferrule, [3] 3/4" NPT, Compression Fitting, Teflon Ferrule, [4] 3/4" NPT, Compression Fitting, Metal Ferrule, [5] 1/2" NPT, Retractable Packing Gland, Graphite Packing, [6] 1/2" NPT, Retractable Packing Gland, Teflon Packing, [7] 3/4" NPT, Retractable Packing Gland, Graphite Packing, [8] 3/4" NPT, Retractable Packing Gland, Teflon Packing |
| Insertion Length (Maximum U-Length) | [1] 6"|152mm, [2] 12"|305mm, [3] 18"|457mm |
| Gas Media & Range | [C] Customized: Air Equivalency Calibration 0.75 to 100 SFPS, 10-50 PSIA, [1] Natural Gas (>90% Methane), [F] Customized: Actual Gas, [A] Standard: Air/Nitrogen Calibration 1.25 to 125 SFPS, 10-50 PSIA, [D] Standard: Air/Nitrogen Calibration 4 to 400 SFPS, 50-165 PSIA, [B] Customized: Air/Nitrogen Calibration 0.75 to 150 SFPS, 10-50 PSIA, [E] Customized: Air/Nitrogen Calibration 2.5 to 400 SFPS, 50-165 PSIA |
| Calibration | [0] Standard 2% Accuracy Calibration, [A] Standard 2% Accuracy Calibration & Extended Temperature Compensation, [M] High Accuracy 1% Calibration, [N] High Accuracy 1% Calibration & Extended Temperature Compensation, [Q] High Accuracy 1% Calibration w/ Vortab (VEL, VFK, VIS, VMR, or VSR), [5] High Accuracy 1% Calibration w/ Vortab (VIP), [T] High Accuracy 1% Calibration & Extended Temperature Compensation w/ Vortab (VEL, VFK, VIS, VMR, or VSR), [6] High Accuracy 1% Calibration & Extended Temperature Compensation w/ Vortab (VIP), [R] High Accuracy 1% Calibration & Flat Flow Profile, [U] High Accuracy 1% Calibration & Extended Temperature Compensation & Flat Flow Profile |
| Transmitter Options | [0] Aluminum Housing w/ Dual 4-20mA Outputs, [A] Stainless Steel Housing w/ Dual 4-20mA Outputs, [A] Stainless Steel Remote Housing w/ Dual 4-20mA Outputs |
| Cable Length | [0] Not Required, [A] 10ft|3m, [B] 25ft|7.6m, [C] 50ft|15m |
| Agency Approvals | [1] FM, FMc, [0] CE Mark Only, [3] ATEX, IECEx |
| SS Tag Plate | Without, [SST1] 2.50 x 0.75"|63.5 x 19.1mm; 2 Lines, [SST2] 2.50 x 0.75"|63.5 x 19.1mm; 3 Lines, [SST3] 2.50 x 1.50"|63.5 x 38.1mm; 6 Lines, [SST4] 3.00 x 1.50"|76.2 x 38.1mm; 6 Lines, [SST5] 3.40 x 1.85"|86.4 x 47.0mm; 6 Lines |